Binder Waste Wood Biomass Boilers

Turning Waste Wood into Profit
HVA cleaning using high-velocity air recirculation (unique to Binder)

Binder Established in 1981

Have a proven history of producing boilers, and have boilers which have been in service for 20 plus years, therefore have provenance of producing boilers which can last for at least the lifetime of the commercial RHI.

Options for HVA cleaning using high-velocity air re-circulation (unique to Binder) or standard compressed air cleaning.

Fully-modulating air dampers

  • All dampers (except grate-isolation damper) use fully modulating action
  • Higher efficiencies (not providing excessive air volume though the boiler, leading to additional dry-gas losses through the flue)
  • More subtle control, providing a more stable combustion profile
  • Competitor boilers often use fixed on-off action

Able to produce boilers to specific requirements

  • Fuel moisture content up to 50% (wet basis)(standard designs 35% and 50%)
  • Fuel sizes up to P125 (standard components to P63)
  • Pressures up to 10bar (3 bar as standard)
  • Temperatures up to 160C (90C as standard)
  • Steam boiler capability and thermal oil.
  • Outputs up to 10MW (7MW standard

Bespoke fuel transport systems

  • Able to overcome level changes, etc
  • Fuel storage to suit fuel and delivery
  • Silos
  • Rotary agitator
  • Hook-lift containers
  • Walking floor

Electrically operated boiler components

  • No oil hydraulics on the boiler
  • Reduced complexity
  • Reduced maintenance
  • Reduced risk due to high pressure oil lines
  • n.b. hydraulic rams still used on large chip extraction

systems (walking floor, hook bins, fuel above P63)

Automatic Ignition

  • Electric up to 35% moisture content
  • Fossil-burner up to 50% moisture content

Exhaust cleaning

  • High velocity air recirculation
  • Cyclone de-duster
  • Option to fit ceramic filters

Lambda Control

  • Adjusts air feed rates
  • Automatically compensates for variances in fuel quality

Boiler controls

  • Full colour graphical touch-screen display
  • Internet connectivity available as standard
  • Bespoke constructed cabinet. Individual components can be replaced
  • Programmable logic controller. Logic can be checked and modified on site

Safety Devices

  • Three-stage burn-back protection
  • Thermostat providing first-stage correction
  • Burn-back flap (or rotary valve) provides air break on power failure
  • Self-acting douse valve and tank provides final stage safety

World-class biomass heating solutions from 500kW to 10MW.

Able to produce boilers to specific requirements

  • Fuel moisture content up to 50% (wet basis) (standard designs 35% and 50%).
  • Able to use Waste Wood Fuels (Grades A, B/C)
  • Fuel sizes up to P125 (standard components to P63).
  • Pressures up to 30bar (3 bar as standard).
  • Temperatures up to 160C (90C as standard).
  • Steam boiler capability.
  • Outputs up to 10MW (7MW standard).

Electrically operated boiler components

  • No oil hydraulics on the boiler.
  • Reduced complexity.
  • Reduced maintenance.
  • Reduced risk due to high-pressure oil lines.
  • n.b. hydraulic rams still used on large chip extraction systems (walking floor, hookbins, fuel above P63).